Background
Rassasy and the Snug Limited commissioned Anderson Acoustics to undertake a noise impact assessment for the installation of supply and extract plant serving a new commercial kitchen at 332 Goring Road, Goring by Sea. The assessment was required to support a planning application and ensure compliance with local authority noise criteria, safeguarding the amenity of nearby residential properties.
Challenge
The main challenge was to evaluate the potential noise impact of the proposed kitchen ventilation system on the nearest noise-sensitive receptors – specifically, the rear facades of 334-340 Goring Road at first-floor level. The site is located in an urban area with existing road traffic noise and other commercial extract fans nearby.
The assessment needed to demonstrate that the new plant would not exceed local authority noise limits, as set out in the Planning Noise Advice Document: Sussex (2023) and British Standard 4142:2014+A1:2019.
What We Did
- Site Survey & Measurements: We conducted a detailed noise survey, capturing ambient and background noise data representative of the nearest residential receptors. Measurements were taken over several days using calibrated class A sound level meters;
- Design Criteria: The assessment set a design criterion that plant noise at the nearest receptors should not exceed 49 dB LAeq,1hr,Tr in line with local authority requirements;
- Noise Modelling: Using 3D noise modelling software (CadnaA), we simulated the propagation of sound from the proposed supply and extract fans, factoring in site topography, building reflections, and worst-case propagation scenarios;
- Analysis: The predicted noise levels at the nearest residential receptors were compared against the measured background levels and local authority criteria.The assessment included detailed calculations of sound power levels, attenuation through ductwork, and consideration of acoustic features.
Result
The noise modelling predicted that the rating level at the nearest residential receptors would be 46 dB LAeq,1hr,Tr – compliant with the local authority criterion of 49 dB LAr,Tr. The assessment concluded that the proposed plant installation would not have an adverse impact on the surrounding residential properties.
We recommended that planning permission should not be refused on noise grounds, providing confidence to both the client and the local authority.