Background
Staticus appointed Anderson Acoustics to review the proposed stick façade specification for the European Space Agency’s International Meeting Facility project in the Netherlands. The objective was to ensure compliance with the project’s acoustic requirements and identify any necessary measures to rectify non-compliance risks.
What we did
The review was undertaken as a desktop study based on available laboratory test reports, comparable systems, and calculation techniques.
Key façade components, including the glazing, framing systems, and opaque panels, were assessed to determine the overall sound insulation performance of the façade against the project requirements. The stick frame system was also assessed in terms of horizontal flanking acoustic performance.
Methodology
The review included:
- Analysis of laboratory test reports and performance data for comparable systems;
- Calculations to estimate expected sound insulation and flanking performance;
- Recommendations for improvements where necessary to meet the required standards.
Assessment of Performance
- Building envelope: The analysis indicated that all façade elements are expected to meet the required sound insulation performance;
- Horizontal Flanking: Assessments of various mullion build-ups identified that junctions where separating walls meet an empty mullion may not meet the required performance and would require improvement.
Recommendations
- Mullion Enhancements: Additional measures were recommended for empty mullions to achieve the required horizontal flanking performance, including the introduction of Fermacell board sandwich infill within the mullions.
Conclusion
The desktop review concluded that the proposed façade specification for the International Meeting Facility project should meet the required sound insulation performance, provided the recommended measures are implemented.